INSTRUCTION OF CHOOSING
LOW VOLTAGE WIRES & CABLES
I.2/ XLPE Insulated power cable
I.2.1/ Cables installed in air:
Current ratings and Voltage drop for CXV , copper conductors, XLPE insulated, unarmoured, PVC oversheathed cables,
Installed in air
Table 4

Ambient temperature 300C
Maximum Conductor temperature 900C
I.2.2/ Cables laid direct in ground:
Current ratings and Voltage drop for CXV/DTA , CXV/WA , copper conductors, XLPE insulated, armoured,
PVC oversheathed cables, Laid direct in ground
Table 5
Tiết diện ruột dẫn
Nom. area of cond. |
Cáp 1 lõi , giáp sợi nhôm
(Single core cable, Aluminium wire armoured ) |
Cáp nhiều lõi, giáp sợi thép
( Multicore cable, Steel wire armoured ) |
2 cáp đặt tiếp xúc trong lưới điện xoay chiều 1 pha
Two cables touching,
single-phase (ac)

|
3 cáp tiếp xúc nhau theo hình 3 lá , 3 pha
Three cables trefoil touching, 3-phase

|
Cáp 2 lõi , lưới điện xoay chiều 1 pha
Two core cable ,
single-phase (ac)

|
Cáp 3 hay 4 lõi
Three or four core Cable

|
Dòng điện định mức
Current ratings |
Độ sụt áp
Approximate volt drop per amp per metre |
Dòng điện định mức
Current ratings |
Độ sụt áp
Approximate volt drop per amp per metre |
Dòng điện định mức
Current ratings |
Độ sụt áp
Approximate volt drop per amp per metre |
Dòng điện định mức
Current ratings |
Độ sụt áp
Approximate volt drop per amp per metre |
|
mm2 |
A |
mV |
A |
mV |
A |
mV |
A |
mV |
| 16 |
142 |
2.9 |
135 |
2.57 |
140 |
2.90 |
115 |
2.60 |
| 25 |
185 |
1.88 |
172 |
1.55 |
180 |
1.90 |
150 |
1.60 |
| 35 |
226 |
1.27 |
208 |
1.17 |
215 |
1.30 |
180 |
1.20 |
| 50 |
275 |
0.99 |
235 |
0.86 |
255 |
1.00 |
215 |
0.87 |
| 70 |
340 |
0.70 |
290 |
0.61 |
315 |
0.70 |
265 |
0.61 |
| 95 |
405 |
0.53 |
345 |
0.46 |
380 |
0.52 |
315 |
0.45 |
| 120 |
460 |
0.43 |
390 |
0.37 |
430 |
0.42 |
360 |
0.36 |
| 150 |
510 |
0.37 |
435 |
0.32 |
480 |
0.35 |
405 |
0.30 |
| 185 |
580 |
0.31 |
490 |
0.27 |
540 |
0.29 |
460 |
0.25 |
| 240 |
670 |
0.26 |
560 |
0.23 |
630 |
0.24 |
530 |
0.21 |
| 300 |
750 |
0.24 |
630 |
0.21 |
700 |
0.21 |
590 |
0.19 |
| 400 |
830 |
0.21 |
700 |
0.19 |
- |
- |
- |
- |
| 500 |
910 |
0.20 |
770 |
0.18 |
- |
- |
- |
- |
| 630 |
1000 |
0.19 |
840 |
0.17 |
- |
- |
- |
- |
| 800 |
1117 |
0.18 |
931 |
0.16 |
- |
- |
- |
- |
| 1000 |
1254 |
0.17 |
1038 |
0.15 |
- |
- |
- |
- |
Basic assumptions and conditions of installation
Soil thermal resistivity 1.2 0C m/W
Ground temperature 15 0C
Dep th of lay ing 0. 5 metre
Maximum operating conductor temperature at rated current: 900C.