Homepage  |  Sitemap  |  Contact us
Language
Head office: 70-72 Nam Ky Khoi Nghia St.,
1st District, Ho Chi Minh City.
Tel: (84.8) 3829 9443 - 3829 2971 - 3829 2972.
Fax: (84.8) 3829 9437.

INSTRUCTION OF CHOOSING
LOW VOLTAGE WIRES & CABLES

 I.1.2/ Cables laid direct in ground ::

Basic assumptions and conditions of installation
Ground thermal resistivity 1.2 0C m/W
Ground temperature 15 0C
Depth of laying 0,5 metre
Maximum operating conductor temperature at rated current: 700C.

Rating factors
Ratings for cables installed direct in the ground are based on values of soil temperature and soil thermal resistivitys, grouping factors and factors for the depths of laying .

Current ratings and Voltage drop for CVV/DTA , CVV/WA, copper conductors, PVC insulated, armoured, PVC oversheathed cables, Laid direct in ground

Table 2

Tiết diện ruột dẫn

Nominal area of conductor

1 lõi (Single core)

2 lõi

Two core



3 và 4 lõi

Three and four core


2 cáp đặt cách khoảng


Two cables spaced

3 cáp tiếp xúc nhau theo hình 3 lá

Trefoil touching


Dòng điện định mức

Current ratings
Độ sụt áp

Approximate volt drop per amp per metre
Dòng điện định mức

Current ratings
Độ sụt áp

Approximate volt drop per amp per metre
Dòng điện định mức

Current ratings
Độ sụt áp

Approximate volt drop per amp per metre
Dòng điện định mức

Current ratings
Độ sụt áp

Approximate volt drop per amp per metre
mm2
A
mV
A
mV
A
mV
A
mV
1,5
33
32
29
25
32
29
27
25
2,5
44
20
38
15
41
17
35
15
4
59
11
53
9,5
55
11
47
9,5
6
75
9
66
6,4
69
7,4
59
6,4
10
101
4,8
86
3,8
92
4,4
78
3,8
16
128
3,2
110
2,4
119
2,8
101
2,4
25
168
1,9
142
1,5
158
1,7
132
1,5
35
201
1,4
170
1,1
190
1,3
159
1,1
50
238
0,97
203
0,82
225
0,94
188
0,82
70
292
0,67
248
0,58
277
0,66
233
0,57
95
349
0,50
297
0,44
332
0,49
279
0,42
120
396
0,42
337
0,36
377
0,40
317
0,35
150
443
0,36
376
0,31
422
0,34
355
0,29
185
497
0,31
423
0,27
478
0,29
401
0,25
240
571
0,26
485
0,23
561
0,24
462
0,21
300
640
0,23
542
0,20
616
0,21
517
0,18
400
708
0,22
600
0,19
693
0,19
580
0,17
500
780
0,20
660
0,18
-
-
-
-
630
856
0,19
721
0,16
-
-
-
-
800
895
0,18
756
0,16
-
-
-
-
1000
939
0,18
797
0,15
-
-
-
-

I.1.3/ Cable run in single way ducts:

  • Basic assumptions and conditions of installation
  • Ground thermal resistivity 1.2 0C m/W
  • Ground temperature 15 0C
  • Depth of laying 0. 5 metre
  • Maximum operating conductor temperature at rated current 700C

Current ratings and Voltage drop for CVV/DTA , CVV/WA copper conductors, PVC insulated, armoured, PVC oversheathed cables, Run in single way ducts

Table 3

Tiết diện ruột dẫn

Nominal area of conductor

1 lõi (Single core)

2 lõi

Two core



3 và 4 lõi

Three and four core


2 cáp : ống tiếp xúc nhau


Two cables : ducts touching

3 cáp: ống xếp theo hình ba lá tiếp xúc nhau

Three cables: ducts trefoil touching


Dòng điện định mức

Current ratings
Độ sụt áp

Approximate volt drop per amp per metre
Dòng điện định mức

Current ratings
Độ sụt áp

Approximate volt drop per amp per metre
Dòng điện định mức

Current ratings
Độ sụt áp

Approximate volt drop per amp per metre
Dòng điện định mức

Current ratings
Độ sụt áp

Approximate volt drop per amp per metre
mm2
A
mV
A
mV
A
mV
A
mV
1,5
30
34
28
27
26
29
22
25
2,5
41
22
35
16
34
17
29
15
4
59
12
48
10.5
45
11
38
9,5
6
69
10
60
7.0
57
7,4
48
6,4
10
90
5.0
84
4.0
76
4,4
64
3,8
16
114
3.4
107
2.6
98
2,8
83
2,4
25
150
2.0
139
1.6
129
1,7
107
1,5
35
175
1.4
168
1.2
154
1,3
129
1,1
50
216
1,0
199
0,88
183
0,94
153
0,82
70
262
0,76
241
0,66
225
0,66
190
0,57
95
308
0,61
282
0,53
271
0,49
228
0,42
120
341
0,54
311
0,47
309
0,40
260
0,35
150
375
0,48
342
0,42
346
0,34
292
0,29
185
414
0,44
375
0,38
393
0,29
331
0,25
240
463
0,40
419
0,34
455
0,24
382
0,21
300
509
0,37
459
0,32
510
0,21
428
0,18
400
545
0,34
489
0,30
574
0,19
490
0,17
500
585
0,32
523
0,28
-
-
-
-
630
632
0,30
563
0,26
-
-
-
-
800
662
0,28
587
0,25
-
-
-
-
1000
703
0,27
621
0,23
-
-
-
-
Page : 1  2  3  4  5  6  7  8
Introduction | Products | Members of CADIVI | Distribution network | News | Contact us
 
© 2006 Vietnam Electric Cable Corporation (CADIVI).
Head office: 70-72 Nam Ky Khoi Nghia St., 1st District, Ho Chi Minh City.
Tel: (84.8) 3829 9443 - 3829 2971 - 3829 2972. Fax: (84.8) 3829 9437. Email: cadivi@cadivi.com.vn