3. Two cores sheathed cable,:CVV,CXV,CXV/FR , CXE/LSF:
| Power (kW) |
Size of CVV |
Size of CXV,CXV/FR,CXE/LSF |
Power (kW) |
Size of CVV |
Size of CXV,CXV/FR,CXE/LSF |
| Up to 1,2 (incl.) |
CVV-2x1 |
CXV-2x1 |
Over 5,9 to 6,6 (incl.) |
CVV-2x6 |
CXV-2x5,5 |
|
Over 1,2 to 2 (incl.) |
CVV-2x1,5 |
CXV-2x1 |
Over 6,6 to 7,7 (incl.) |
CVV-2x8 |
CXV-2x6 |
| Over 2 to 2,6 (incl.) |
CVV-2x2 |
CXV-2x1,5 |
Over 7,7 to 9 (incl.) |
CVV-2x10 |
CXV-2x8 |
| Over 2,6 to 3,3 (incl.) |
CVV-2x2,5 |
CXV-2x2 |
Over 9 to 9,6 (incl.) |
CVV-2x11 |
CXV-2x10 |
| Over 3,3 to 3,7 (incl.) |
CVV-2x3,5 |
CXV-2x2,5 |
Over 9,6 to 12 (incl.) |
CVV-2x14 |
CXV-2x11 |
| Over 3,7 to 4,4 (incl.) |
CVV-2x4 |
CXV-2x3,5 |
Over 12 to 14 (incl.) |
CVV-2x16 |
CXV-2x14 |
| Over 4,4 to 5,9 (incl.) |
CVV-2x5,5 |
CXV-2x5,5 |
Over 14 to 22 (incl.) |
CVV-2x25 |
CXV-2x22 |
4. Three or four cores sheathed cable :CVV,CXV,CXV/FR , CXE/LSF:
Power (kW) |
Size of
CVV |
Size of CXV,CXV/FR,CXE/LSF |
Power (kW) |
Size of CVV |
Size of CXV,CXV/FR,CXE/LSF |
Up to 4,6 (incl.) |
CVV-3x1,5 |
CXV-3x1 |
Over 13 to 14,5 (incl.) |
CVV-3x6 |
CXV-3x5,5 |
Over 4,6 to 7,2 (incl.) |
CVV-3x2,5 |
CXV-3x1,5 |
Over 14,5 to 17 (incl.) |
CVV-3x8 |
CXV-3x6 |
Over 7,2 to 9,2 (incl.) |
CVV-3x3,5 |
CXV-3x2,5 |
Over 17 to 22,5 (incl.) |
CVV-3x10 |
CXV-3x8 |
Over 9,2 to 10,5 (incl.) |
CVV-3x4 |
CXV-3x3,5 |
Over 22,5 to 29,5 (incl.) |
CVV-3x14 |
CXV-3x11 |
Over 10,5 to 13 (incl.) |
CVV-3x5,5 |
CXV-3x5,5 |
Over 29,5 to 35,5 (incl.) |
CVV-3x16 |
CXV-3x14 |
IV Use building wire and cable of CADIVI in residential appliances :
For building : wiring is embedded in wall, in floor…
Because in the building, industry equipment installed are off heavy-duty ( elevator, water pump, air-conditioner,…) , electrical must be stable, safe and reliable, comply with fire regulations , so the following wires and cables are used :
- VC, CV, CX or CVV, CXV used as distribution-line
- CVV, CXV used as air-conditioner, elevator, water pump…
- CX/FR, CXE/FR, CXE/LSF used in critical circuits that must continue to operate in case of a fire e.g. fire alarms, emergency lifts, pump circuits etc
|